A version of the DNP.CFG file got released that had the tag names for the PLC binary outputs and analog outputs incorrect.
To correct this, locate the tags labeled: "PLC binary output". To correct this, add an S on the end to make it plural.
Then locate the tags labeled: "PLC analog output", and make the same correction. Add an S to make it plural, so it reads "PLC analog outputs", and the other tag reads "PLC binary Outputs". That will fix the problem.