In the configuration of the GOOSE message for the IEC-61850 protocol on a GE relay, it is necessary to configure the GOOSE message to go to the GOOSE MAC address, rather than the actual MAC address of the relay. Attached is a screen capture showing the configuration scr...
Read moreWhen using a .ICD file to configure devices on an IEC 61850 network there are potential issues in importing the file into the 61850 Configuration Manager software. There are a couple of things to look at. 1) The configuration tool ac...
Read moreIf MMS reports are not working with a ProSoft IEC 61850 client gateway please review the following points, as the most common reasons are listed below:1.Mismatch between the IEC 61850 client and server configuration: verify that the report configuration loaded in the Server and t...
Read moreYes, the Ethernet port(s) will work with either cross-over cables or standard Ethernet patch cables to a switch or another device....
Read moreMost ProSoft products which either go in a Rockwell PLC rack (InRAx modules) or communicate over EtherNet/IP (EIP), most of these products do not require an .EDS file for proper operation. Because of this. we do not provide .EDS files for every product which could support them. ...