Are there any known problems using RSLogix500, versions 7.1, 7.2 or 7.3 with ProSoft's 3250-L532M SLC 5/03 RTU processor?

Search KB

Categories

Yes!  Allen-Bradley has released information regarding a problem that arises in RSLogix500, versions 7.1, 7.2 and 7.3, when you try to use the "Read I/O Config" feature or when you download a program to the ProSoft 3250-L532M SLC 5/03 RTU.  The problem manifests itself as a change in processor firmware version.  If you download a program to the 5/03 RTU and then upload it back, you will notice the selected processor revision has been changed.  If you try to run the downloaded program, the 5/03 RTU faults.

Rockwell Software has now released RSLogix500, version 7.30.10, in which this problem has been corrected.

The work-around until AB fixes this is to manually change the processor back to  "1747-L532C/D 5/03 CPU - 16K Mem. OS302"  before you try to download it back to the SLC 5/03 RTU.