The attached document lists the changes made to hardware between rev A and rev B of the PC56....
Read moreDCOM configuration issues are the most likely causes for connectivity issues from/to the Echo Historian & OPC/SLS servers offered on the PC56/PC56CE/7000 AppSrvCE solutions. This relates to how Windows network clients validate each others addresses.For two DCOM components on ...
Read moreYou can enable/disable the logging feature in ArchestrA Logger and control the logging features by the following attachment.(see attachment)...
Read moreWe do not offer a PC56 loaded with Linux. It is possible to install Linux on the PC56, but the drivers to handle the backplane and the special features (LED screen, switch, temperature sensor) are not available, so it will behave like any embedded PC.However the MVI56E-LDM (Linux...
Read moreAll redundancy will be configured and handled in the ControlLogix (CLX) equipment. Besides a redundant-capable CPU, each chassis will need a 1756-CRM module (this takes two slots in a CLX rack), plus an ENBT module in each chassis. This configuration uses all fo...
Read moreThis is caused by a bug in Microsoft Embedded Visual C.Download and install Windows XP Service Pack 3 from Microsoft, then reinstall the PC56-CE development kit....
Read moreThe current shipping version of Windows CE installed on ProSoft's PC56-CE solutions is Windows CE 5.0, catalog rev B01....
Read moreUnfortunately, it is not possible to add the 40Gb IDE drive to a PC56-XP that came with a 4Gb Compact Flash (CF) card installed. Due to limitations of the PC56 BIOS, you can use either the CF card or the IDE drive; but not both.If you originally ordered your PC56-XP with the 4Gb ...
Read moreUnfortunately, it is not possible to add the 40Gb IDE drive to a PC56-XP that came with a 4Gb Compact Flash (CF) card installed. Due to limitations of the PC56 BIOS, you can use either the CF card or the IDE drive; but not both.If you originally ordered your PC56-XP with the 4Gb ...
Read morePlease see the Technical Note attached....
Read moreThe PC56 to echo configurator is able to browse for tags in a specific device only when the echo interface is stopped. By default the interface is always up and running, so to be able to browse for tags the interface has to be stopped.To stop the echo interface, Start -> All P...
Read more