Belden 9841 or 9842, or equivalent from another manufacturer, is recommended for RS-485 wiring....
Read moreModule is shipped in RS-232 mode. Seeing communication errors. Error: "-11" not seeing data enabling communication Set port jumper to RS-485 position Confirm wiring polarity and integrity Confirm communication parameters for port matches other device ...
Read moreBelden 9841 or 9842 is recommended for RS-485 wiring....
Read moreThe ProLinx modules are shipped with adapter cables which convert the Mini-DIN connector on the module to a standard DB9 male connector....
Read moreThe MVI modules are shipped with adapter cables which convert the RJ-45 connector on the module to a standard DB9 male connector.Related Keywords:RJ45 RJ-45 MVI46 MVI56 MVI71...
Read moreNo, generally terminating resistors are not required, and can actually cause communication problems on the network. Every network is different, and has different requirements, but it is best to start without terminating resistors, and add then only if necessary.If terminating res...
Read moreThe Prosoft Modbus device port can be configured for either RS-232, RS-422, or RS-485. RS-232 allows a point-to-point connection, with 50 feet being the maximum length. RS-422 allows a multi-drop connection,with a maximum of 10 devices on the network. The maximum total distance i...
Read moreNo, the 1451-9F adapter has pins 7 and 8 jumpered internally....
Read moreNot generally, and most of the time they generate more problems on the network. Our recommendation is to setup your RS-485 network without terminating resistors initially. If communication problems are seen which can be attributed to signal echoes or reflections, then a 120 OHM t...
Read moreNo. The terminal adapters supplied are for use on RS-422 or RS-485 networks only.Related Keywords:ProSoft ProLinx serial communications...
Read moreThe Prosoft communication module supports 2-wire RS-485 communications. Although not officially supported, it is possible to get at least some 4-wire RS-485 devices to communicate using the following steps. Jumper the receive + and transmit + pins together. Jumper the receive ...
Read moreYes, you may. Just be sure to use PROFIBUS specific cable (Belden 3079a or equivalent) and proper connectors designed specifically for PROFIBUS DP. At least two of the connectors (one at each end of the cable) will require PROFIBUS termination switches. Related Keyword...
Read moreOddly enough, yes, it can. That rubber boot is meant to protect the plastic clip on the RJ45 connector from being snagged and broken when the cable is pull though tight spaces. However, it can slide back and forth on the cable, as well.If it slides a little too far forward, towar...
Read moreThe attached document shows the pin-out diagrams for serial communications....
Read moreThe part number for reordering the RJ45 to DB9 adapter cable provided with PLC serial modules is Cable 14.Pinout for the DB9 side: This is a straight thru adapter cable, pin 1-1, 2-2, 3-3, etc. Pin 9 on the DB9 side is not used.For the RJ45 side, while facing the module, the...
Read moreThe pins in the RJ-45 jacks on the MVI-series modules are numbered 1, 2, 3,...8, top to bottom. Pin 1 is the topmost pin in the jack, pin 8 is the bottommost pin in the jack. You can eliminate the RJ45-to-DM9M adapter cable and wire your communication cables directly to the RJ45 ...
Read moreProSoft inRAx, ProTalk, and ProLinx solutions do not provide any power via their serial or Ethernet ports.In the case of serial devices, if external adapters or adapter cables are used that expect to get power from the ProSoft solution's serial port, those devices will not work a...