PLX82-EIP-PNC Product Photo - EtherNet/IP to PROFINET controller gateway module

EtherNet/IP™ to PROFINET Controller Gateway

PLX82-EIP-PNC

The EtherNet/IP™ to PROFINET Controller Gateway allows you to connect two giants of industrial automation through secure, high-speed communications. The gateway provides EtherNet/IP-based controllers the ability to control up to 36 PROFINET RT devices such as field I/O, drives, HMIs, and controllers.

The PLX82-EIP-PNC gateways are stand-alone DIN-rail mounted units that provide two Ethernet ports for communications, remote configuration, and diagnostics. The onboard SD Card slot (SD card optional) is used for storing configuration files that can be used for recovery, transferring the configuration to another gateway, or general configuration backup.

Imágenes

Click on image(s) to enlarge
Drag with the mouse. Click for close.

Características y Beneficios

  • Multiple I/O connections allow for high-speed control for large PROFINET I/O systems
  • Isolated Ethernet ports allow devices on different protocols to be on different subnets
  • ODVA-approved
  • PROFINET v2 certification with PROFINET class A compliance
  • Field-tested with multiple PROFINET devices from multiple vendors
  • Remotely view and diagnose EtherNet/IP and PROFINET networks
  • Embedded EDS AOP provided to allow for seamless integration to Studio 5000 and RSLogix™ 5000
  • Using EtherNet/IP I/O connections, no ladder programming is required

Especificaciones

EtherNet/IP® Specifications

Specification

Description

Class 3 Server Connections

5

Supported PLC Types

PLC2, PLC5, SLC, CLX, CMPLX

Class 3 Client Connections

Connected: 2
 Unconnected: 1

Class 1 I/O Connections

8

Max I/O connection size In/Out

248/248

Min RPI time

2 ms (1 connection)

8 ms (8 connections)

CIP Services Supported

0x4C - CIP Data Table Read

0x4D - CIP Data Table Write

Command List

Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count.

 

PROFINET Specifications

Specification

Description

Driver Type

Class 1 RTC, Class 1 RTA

PROFINET I/O Data

3840 bytes IN, 3840 bytes OUT

Exchange Types

Cyclic Real-time (RT) and Acyclic Data

PROFINET Devices

Max: 36 | Max data per device: 1440 bytes in/out

Hardware

Specification

Description

Power Supply

24 VDC nominal
10 to 36 VDC allowed
Positive, Negative, GND Terminals

Current Load

24 VDC nominal @ 400mA

10 to 36 VDC @ 610mA maximum

Operating Temperature

0° to 50°C (32° to 122°F )

Storage Temperature

-10° to 70°C (-14° to 158°F )

Relative Humidity

5% to 95% RH with no condensation

Shock

Operational: IEC 60068-2-27; 15G @ 11ms, 3-Axis

Non-Operational: IEC 60068-2-27; 30G @ 18ms, 3-Axis

Vibration

IEC 60068-2-6; 5G @ 10 to 150 Hz

Dimensions
(H x W x D)

5.52 x 2.06 x 4.37 in
14.01 x 5.24 x 11.09 cm

Ethernet Port

10/100Mbit RJ45 Connector Electrical Isolation 1500 Vrms at 50 to 60 Hz for 60 seconds.

Shipped With Each Unit

2.5 mm screwdriver, J180 Power Connector

Certificaciones

UL Certificate of Compliance 225,88 kB Última Modificación 16.11.2022
CB Safety 338,32 kB Última Modificación 27.04.2022
Declaration of Conformity (RoHS/CE) 114,24 kB Última Modificación 01.06.2022
PROFINET Certification 324,14 kB Última Modificación 10.08.2017
ODVA EtherNet/IP - Declaration of Conformity 183,48 kB Última Modificación 09.11.2020
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1,92 MB Última Modificación 11.02.2022
ATEX Letter of Conformity 105,11 kB Última Modificación 12.05.2022
Declaration of REACH Compliance 145,49 kB Última Modificación 01.06.2022