PLX51-DF1-MSG Product Photo

DF1 Messaging Module

PLX51-DF1-MSG

The DF1 messaging module can be used in applications requiring DF1 to Logix messaging. The module can be used to communicate between PC’s or PLC’s using DF1™ or EtherNet/IP™.

Have a bunch of MicroLogix or SLC’s in your water or waste water treatment facility? DF1 Radio Modem protocol can be used for migrating old SLC’s and MicroLogix PLC’s to newer Logix based platforms over leased line modems. Start migrating the legacy equipment to new Logix based equipment with the help of ProSoft Technology’s DF1 Messaging Module.

Imágenes

Click on image(s) to enlarge
Drag with the mouse. Click for close.
Drag with the mouse. Click for close.
Drag with the mouse. Click for close.
Drag with the mouse. Click for close.

Características y Beneficios

  • DF1 Radio Modem with support for store and forward functions
  • Intelligent routing to ControlLogix® or CompactLogix™ from PLC-5®, SLC, MicroLogix controllers and SCADA systems
  • Direct-to-tag technology simplifies data mapping, reducing configuration time
  • Secure module configuration via on module switch
  • Can be used in a redundant ControlLogix system
  • Built-in packet analyzer for DF1 networks

Especificaciones

EtherNet/IP

Description

Connector

RJ45

Conductors

CAT5 STP/UTP

ARP Connections

Max 20

TCP Connections

Max 20

CIP Connections

Max 10

Communication Rate

10/100 Mbps

Duplex Mode

Full / Half / Auto-Negotiate

Auto MDIX

Yes

 

 

DF1

Description

Protocol

DF1 Full Duplex, DF1 Half Duplex, DF1 Radio Modem

Baud Rates

1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

Parity

None, Even, Odd

Data Bits

8

Stop Bits

1

Error Detection

CRC, BCC

Embedded Response

Auto, On

Bridge Mode Mapping

Max 20 routes

Slave Mode Mapping

Max 20 routes

Slave Mode Message Support

PLC-5 Typed Read, PLC-5 Typed Write, SLC Typed Read, SLC Typed Write, PLC-2 Unprotected Read, PLC-2 Unprotected Write, PLC-2 Unprotected Bit Write

Scheduled Tag Mode Message Support (Master)

PLC-5 Typed Read, PLC-5 Typed Write, SLC Typed Read, SLC Typed Write

Hardware

Specification

Description

Enclosure

Plastic

Enclosure Rating

IP20, NEMA/UL Open Type

Dimensions (H x W x D)

101.0 x 22.5 x 120.0 mm

Power Requirements

Input: 10 to 28 VDC,

(70 mA @ 24 VDC / 130 mA @ 10 VDC)

Power Consumption

1.7 W

Power Connector

3-way terminal

Conductors

24 to 18 AWG

Temperature

-20°C to 70°C

Earth Connection

Yes, terminal based

Emissions

IEC61000-6-4

ESD Immunity

EN 61000-4-2

Radiated RF Immunity

IEC 61000-4-3

EFT/B Immunity

EFT: IEC 61000-4-4

Surge Immunity

Surge: IEC 61000-4-5

Conducted RF Immunity

IEC 61000-4-6

Certificaciones

ATEX Letter of Conformity 101,57 kB Última Modificación 12.05.2022
CB Safety 340,56 kB Última Modificación 04.09.2019
Declaration of Conformity (RoHS/CE) 139,57 kB Última Modificación 16.11.2022
ODVA EtherNet/IP Declaration of Conformity 135,16 kB Última Modificación 15.10.2020
UL/cUL; Class1, Div 2 236,84 kB Última Modificación 04.09.2019
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1,92 MB Última Modificación 11.02.2022
Declaration of REACH Compliance 128,14 kB Última Modificación 16.11.2022
Korean KC Registration 282,43 kB Última Modificación 28.04.2022