The PLX51-HART-4I allows users to easily connect their existing HART-compatible field devices to EtherNet/IP™, Modbus® TCP/IP, and DNP3 Ethernet networks. The module can be used to connect HART Input devices such as process instruments into an Ethernet network.
The PLX51-HART-4I supports up to 4 channels of HART communication, as well as Analog 4-20 mA signals for real-time process variables to/from the HART-compatible device.
| Specification |
Description |
| Number of Channels |
4 |
| ADC Resolution |
12 bit |
| Input Impedence |
247.5 Ω |
| Accuracy (Calibrated 25°C) |
< 0.15 % |
| Accuracy (Uncalibrated) |
< 0.30 % |
| Range |
0 to 22 mA |
| Current limit |
34 mA |
| Specification |
Description |
| Connector |
RJ45 |
| Conductors |
CAT5 STP/UTP |
| ARP Connections |
Max 20 |
| TCP Connections |
Max 20 |
| CIP Connections |
Max 10 |
| Communication Rate |
10/100 Mbps |
| Duplex Mode |
Full / Half |
| Auto MDIX |
Yes |
| Specification |
Description |
|
Function Codes |
1: Read Coils |
| Specification |
Description |
| Mode Supported |
DNP3 Outstation |
| Application Functions Supported |
Read |
| Unsolicited Response Supported |
No |
| DNP3 Events Supported |
No |
| Specification |
Description |
| Key Change Method Supported |
Pre-shared |
| MAC Algorithms Supported |
HMAC SHA-1 encryption (4 octets, serial) – for legacy support |
| Key Wrap Algorithms Supported |
AES-128 Key Wrap |
| Aggressive Mode Supported |
No |
| Specification |
Description |
| Enclosure Rating |
IP20, NEMA/UL Open Type |
| Temperature |
-20 to 70 °C |
| Earth connection |
Yes, terminal based |
| Emissions |
IEC61000-6-4 |
| ESD Immunity |
EN 61000-4-2 |
| Radiated RF Immunity |
IEC 61000-4-3 |
| EFT/B Immunity |
EFT: IEC 61000-4-4 |
| Surge Immunity |
Surge: IEC 61000-4-5 |
| Conducted RF Immunity |
IEC 61000-4-6 |
| Specification |
Description |
| Enclosure |
Plastic |
| Dimensions (H x W x D) |
101 x 22.5 x 120 mm |
| Power Requirements |
12 to 28 VDC 35mA @ 24 VDC - With no field devices attached 130mA @ 24 VDC - With 4 field devices at 22mA each 64mA @12 VDC - With no field devices attached 160mA @ 12 VDC - With 4 field devices at 22mA each |
| Power Consumption |
0.9 W - With no field devices attached |
| Power Connector |
3-way terminal |
| Connector (Analog) |
2-way terminal |
| Conductors |
24 to 18 AWG |
| CB Safety | 350,20 kB | Última Modificación 05.12.2018 |
| ATEX Letter of Conformity | 84,70 kB | Última Modificación 12.05.2022 |
| Declaration of Conformity (RoHS/CE) | 139,57 kB | Última Modificación 16.11.2022 |
| ODVA EtherNet/IP Declaration of Conformity | 135,16 kB | Última Modificación 15.10.2020 |
| UL/cUL; Class1, Div 2 | 236,84 kB | Última Modificación 04.09.2019 |
| Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) | 1,92 MB | Última Modificación 11.02.2022 |
| Declaration of REACH Compliance | 128,14 kB | Última Modificación 16.11.2022 |