5201-DFNT-104C

EtherNet/IP to IEC60870-5-104 Client Communication Gateway

5201-DFNT-104C

Descontinuado: Producto no disponible en stock. More Info

The ProLinx EtherNet/IP to IEC60870-5-104 Client gateway creates a powerful connection between an EtherNet/IP network and IEC 104 server devices. The stand-alone, DIN-rail-mounted protocol gateway provides one Ethernet port.

The EtherNet/IP protocol supports the Explicit Messaging implementation of the protocol (PCCC-type messages). User-configurable as both a Client and a server, the EtherNet/IP port is a very powerful data transfer tool.

The IEC60870-5-104 Client protocol implementation allows the transfer of monitor and control data to and from remote servers.

Características y Beneficios

Powerful network integration

  •  Allows movement of data between dissimilar networks using two communication protocols on one gateway
  •  Protocols share access to a common memory database to exchange data between networks
  •  View diagnostic data for both networks from a single configuration/debug port

EtherNet/IP Client and Server

  •  Integrate with widely available Rockwell Automation and third-party products and services worldwide
  •  Client/server Explicit Messaging communication supported (PCCC-type messages)
  •  Five server connections
  •  One client connection provides up to 100 commands

IEC 60870-5-104 Client

  •  Four connections for remote servers
  •  Supports up to two Common ASDU Addresses per server
  •  Supports monitored and control data
  •  Supports up 500 commands to the remote servers
  •  Timestamp events are available to the other protocol through the mailbox feature

Especificaciones

General Specifications – IEC 60870-5-104C

The ProLinx family EtherNet/IP to IEC 60870-5-104 Client communications module creates a powerful connection between an EtherNet/IP network and IEC 104 server devices. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Ethernet port.

General Specifications - EtherNet/IP™

The EtherNet/IP™ protocol is one of the primary connectivity tools used by different

Rockwell Automation® platforms.

The Explicit Messaging aspect of the protocol has been implemented to provide

asynchronous data transfer between the ProLinx gateway and Rockwell

Automation hardware.

Supported PLC Types

PLC-2®, PLC-3®, PLC-5®, SLC™500, ControlLogix®,

CompactLogix™, and MicroLogix™

 

Messaging Types

As a Client, PCCC Explicit Messaging

As a Server, PCCC or CIP Explicit Messaging

Command Sets

PLC-2/PLC-3/PLC5 Basic Command Set

PLC5 Binary Command Set

PLC5 ASCII Command Set

SLC500 Command Set

 

EtherNet/IP™ Server

In server mode, the gateway accepts commands from one or more Clients to read/write data stored in the gateway’s internal registers.

Number of Connections

5

Supported PLC Types

PLC2, PLC5, SLC and ControlLogix file types

supported

Internal Database

Data Table File Size: 100 or 1000 words

Data Table File Start: N10 to N109 (based on file

size set to 100) or

N10 to N19 (based on file set to 1000)

CIP Services Supported

0x4C - CIP Data Table Read

0x4D - CIP Data Table Write

 

EtherNet/IP™ Client

In Client mode, the gateway controls the read/write data transfer between the gateway and other EtherNet/IP devices.

Number of Clients Supported

1

Command List

Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count.

Polling of Command List

User-configurable polling of commands, including disabled, continuous and on change of data (write only).

Other Configurable Parameters

Number of Commands (up to 100 per Client)

Min Command Delay

Response Timeout

Retry Count

Command Error Pointer

 

Functional Specifications - IEC 60870-5-104 Client

  • Operating in the Client mode, the gateway generates commands to a server device to read/write data stored in the gateway's internal registers.
  • The IEC 60870-5-104 Client communication protocol is built in accordance to the approved IEC specification.
  • The gateway functions as a Client on the network supporting monitored and control data from IEC 60870-5-104 servers on the network.
  • The gateway supports unsolicited messages, either cyclic or spontaneous.
  • The gateway supports clock synchronization commands.
  • The gateway supports Group interrogation (Global, General 1 to 16, Global Counters, Counters 1-4).
  • The gateway supports up to 4 Client connections.

Supported Message Types

Accepts Client Monitor and Control Messages

Supports all Edition 2 Causes of Transmission

Supported Data Types

Monitor Points:

M_SP_NA

M_DP_NA

M_ST_NA

M_BO_NA

M_ME_NA, NB, NC

M_IT_NA

Control Points:

C_SC_NA

C_DC_NA

C_BO_NA

C_RC_NA

C_SE_NA, NB, NC

 

Maximum number of points

(per Data Type)

 

1000 Points for all Supported Data Types, except

4000 total data words, maximum

Maximum number of commands

500 commands maximum for all four clients

Event Message Support

Timestamp events are transferred to the other protocol through the mailbox feature.

Configurable Parameters

t1 timeout set value

t2 timeout set value

t3 timeout set value

k (maximum queue)

w (latest ack threshold)

Especificaciones

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

Hardware

Specification

Description

Power Supply

24 VDC nominal
18 to 32 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade

Current Load

500 mA max @ 32 VDC max

Operating Temperature

-4° F to 122° F (-20° C to 50° C)

Storage Temperature

-40° F to 185° F (-40° C to 85° C)

Relative Humidity

5% to 95% (with no condensation )

Dimensions

Standard:
 5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Extended:
 5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)

LED Indicators

Power and Module Status
Application Status
Serial Port Activity
Serial Port Error Status

Configuration Serial Port

DB-9M RS-232 only
No hardware handshaking

Ethernet Port (Ethernet modules only)

10Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Application Ports

Modbus Plus Connector
Two DB9 Female Standard Modbus Plus connectors

Serial Port Isolation

2500 V RMS port signal isolation per UL 1577
3000 VDC min. port to ground and port to logic power isolation

Shipped with Each Unit

Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)

Descargas

DFNT-104C Datasheet 232,49 kB Última Modificación 25.06.2013
DFNT Protocol Manual 2,03 MB Última Modificación 24.07.2013
ProSoft Configuration Builder (PCB)
LifeCycle Letter 5000 Selected Series 114,23 kB Última Modificación 13.11.2023
104C Protocol Manual 1,80 MB Última Modificación 23.05.2014
ProLinx Reference Guide 1,52 MB Última Modificación 12.11.2014

Certificaciones

CB Safety 35,78 kB Última Modificación 27.04.2022
Korean KC Registration 807,00 kB Última Modificación 13.03.2020
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1,92 MB Última Modificación 10.07.2020
UL/cUL; Class 1, Div 2 1,08 MB Última Modificación 31.03.2020
UL Certificate of Compliance - Canada 1,10 MB Última Modificación 16.11.2022