MVI56-Serial Picture

BASIC Communication Module

MVI56-BAS

Disponibilidad Limitada: Producto en stock limitado. More Info

This single-slot module is a powerful solution that allows the large installed base of legacy BASIC programs for the 1771-DB and 1747-BAS modules to be migrated to the ControlLogix platform with minimal effort.

Características y Beneficios

  • Create BASIC programs to transfer data between the ControlLogix and the MVI56-BAS module.
  • Create foreign device interface for specific applications and easily integrate the device with the ControlLogix processor.
  • Interface to many devices that use ASCII interface to a ControlLogix backplane such as modems, printers, bar code readers, and scales.
  • Save ControlLogix processor memory by running math algorithms.
  • The module acts as DF1 full-duplex device or a DF1 half-duplex slave.

Especificaciones

General Specifications

  • Single Slot - 1756 backplane compatible
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module.
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
  • Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
  • Local or remote rack

Functional Specifications

The BASIC programs are stored in the MVI56-BAS Compact Flash disk
allowing the user to easily backup the BASIC programs to another Compact
Flash disk or to a local PC. Up to 24065 Bytes of RAM are available.

The module contains three ports:

  • DH-485: DH-485 communication or BASIC program transfer
  • PRT1: ASCII communication or program port
  • PRT2: ASCII communication or DF1 communication

The user can either create the BASIC programs using the command line, then
save it to Compact Flash, or create the program on a PC and download it to the
MVI56-BAS module. The user can also configure the module to execute a
BASIC program automatically at power up.

  • Supports BASIC-52 Programming language
  • Stores BASIC programs on Compact Flash disk
  • Supports 24064 bytes of RAM
  • Easy BASIC program backup

DF1 Communications

  • PRT2 can be enabled and configured for DF1 Communications through BASIC calls
  • Uses ladder logic to transfer data between the DF1 device and the ControlLogix processor
  • PRT2 port can be configured to act as a full-duplex device or half-duplex slave

The MVI56-BAS can send the following DF1 commands:

  • PLC-2 unprotected READ command
  • PLC-2 unprotected WRITE command
  • PLC-3 word range READ command
  • PLC-3 word range WRITE command
  • PLC-5 typed READ command
  • PLC-5 typed WRITE command

The MVI56-BAS accepts the following commands:

  • PLC (word range writes)
  • PLC (typed writes)
  • PLC (unprotected write)
  • SLC 5/02 (unprotected write)
  • SLC 5/02 (typed writes)

DH-485 Communications

  • The MVI56-BAS DH-485 port can be used to interface the ControlLogix processor with DH-485 Devices
  • Rockwell Automation AIC+ device is required (user-supplied)
  • Ladder logic is required to transfer data between the ControlLogix processor and remote data file or common interface file

 

Hardware

Specification

Description

Backplane Current Load

800 mA @ 5.1 VDC
3 mA @ 24 VDC

Operating Temperature

32° F to 140° F (0° C to 60° C)

Storage Temperature

-40° F to 185° F (-40° C to 85° C)

Shock

30 g Operational
50 g non-operational

Vibration

5 g from 10 to 150 Hz

Relative Humidity

5% to 95% (without condensation)

LED Indicators

Module Status
Backplane Transfer Status
Application Status
Serial Activity

Debug/Configuration port (CFG)

CFG Port (CFG)

RJ45 (DB-9M with supplied cable)
RS-232 only

Application ports (PRT1 & PRT2)

Full hardware handshaking control, providing radio, modem and multi-drop support

Software configurable communication parameters

Baud rate: 110 to 115,200 baud, depending on protocol
RS-232, 485 and 422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds

App Ports (P1,P2) (Serial modules)

RJ45 (DB-9M with supplied cable)
RS-232 handshaking configurable
500 V Optical isolation from backplane

Shipped with Unit

RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable

Certificaciones

ATEX Letter of Conformity 79,81 kB Última Modificación 12.05.2022
CB Safety 41,99 kB Última Modificación 26.02.2020
Declaration of Conformity (RoHS/CE) 137,73 kB Última Modificación 20.05.2022
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1,92 MB Última Modificación 10.07.2020
Korean KC Registration 616,34 kB Última Modificación 13.03.2020
UL/cUL; Class 1, Div 2 1,12 MB Última Modificación 27.02.2019
UL/cUL; Class 1, Div 2 (Canada) 1,14 MB Última Modificación 27.02.2019
Declaration of REACH Compliance 133,82 kB Última Modificación 20.05.2022