The J1939 Router enables data exchange between SAE J1939 devices and a Logix controller via EtherNet/IP™.
The J1939 Router provides auto extraction and scaling of SPNs (Suspect Parameter Number) for standard SAE (Society of Automotive Engineers) defined PGNs (Parameter Group Number). These SPNs can then be mapped to Logix UDTs Tags. This allows the user to create a J1939 Router project with all the required PGNs and then export a Logix L5X file with the required Tags and UDTs for that specific J1939 Router project. This L5X file can be imported into Logix.
The J1939 Router allows the user to select standard specification defined PGNs (e.g. PGN 61444 – Electronic Engine Controller 1) from a list in the Slate software. This will automatically build the mapping and scaling for each SPN which can be downloaded to the module. The user can then export a Logix UDT from the Slate software which maps the PGN selected. This can be imported into a Logix application and used as a destination tag for the configured PGN (greatly simplifying the application setup).
The Slate Configuration Utility software is used for configuration and troubleshooting of the module. The stand-alone configuration utility allows users to define the setup and configuration of the J1939 Router module, connections with controllers and devices.
EtherNet/IP Network
Specification |
Description |
Connector |
RJ45 |
Conductors |
CAT5 STP/UTP |
ARP Connections |
Max 20 |
TCP Connections |
Max 20 |
CIP Connections |
Max 10 |
Communication Rate |
10/100 Mbps |
Duplex Mode |
Full / Half |
Auto-MDIX Support |
Yes |
J1939 Network
Specification |
Rating |
Connector |
5-way terminal, 5.08 mm pitch. |
Max PGN Mapping |
40 |
Max PGN Size Supported |
480 bytes per PGN |
Supported Baud Rates |
250k, 500k |
Arbitrary Address Capable |
Yes |
Support for Multi-packets |
Yes |
Configurable J1939 Name |
Yes |
Specification |
Rating |
Power Supply |
Input: 10 to 28 VDC, (70 mA @ 24VDC) |
Power Consumption |
1.7 W |
Dimensions (H x W x D) |
101.0 x 22.5 x 120.0 mm |
Connector |
5-way terminal, 5.08 mm pitch. |
Conductors |
24 to 18 AWG |
Enclosure Rating |
IP20, NEMA/UL Open Type |
Temperature |
-20 to 70 °C |
Humidity |
0 to 95% RH, non-condensing |
Earth Connection |
Yes, terminal based |
Emissions |
IEC61000-6-4 |
ESD Immunity |
EN 61000-4-2 |
Radiated RF Immunity |
IEC 61000-4-3 |
EFT/B Immunity |
IEC 61000-4-4 |
Surge Immunity |
IEC 61000-4-5 |
Conducted RF Immunity |
IEC 61000-4-6 |
CE Declaration of Conformity (CE, UKCA, RoHS, UL) | 336,73 kB | Last Modified 09.03.2023 |
UL/cUL; Class1, Div 2 | 233,29 kB | Last Modified 09.03.2023 |
ODVA Certification | 127,96 kB | Last Modified 12.05.2023 |