PTQ - Client

IEC 60870-5-104 Client for Quantum

PTQ-104C

Disponibilidad Limitada: Producto en stock limitado. More Info

The IEC 60870-5-104 Client Communication Module allows compatible processors to interface easily with other IEC 60870-5-104 protocol-compatible servers such as RTU's and IED devices. Developed under license from Schneider Electric, the module incorporates proprietary backplane technology that enables powerful data access to the Quantum processor and can even be used in Quantum Unity Hot-Standby applications.

The PTQ-104C module acts as an input/output module between the IEC-60870-5-104 Ethernet network and the Quantum processor. Data transfer between the module and the processor is asynchronous from the actions on the network. Databases are defined by the user for the module to hold data as required by the protocol, passing this information over the backplane to the Quantum CPU.

Imágenes

Click on image(s) to enlarge
Drag with the mouse. Click for close.
Drag with the mouse. Click for close.

Características y Beneficios

The PTQ-104C Hot-Standby allows the module to be controlled by a secondary Quantum processor in the event of a main processor failure. The Personality Module incorporates a non-volatile Compact Flash memory for storing the module's setup and network configuration data (or personality). This allows restoring of the module by simply exchanging the Personality Module with no need to use a PC or re-configure. The module supports up to four clients and has the ability to poll data from four unique devices at the same time. Event time-stamping can be configured for more accurate information for sequence of events reporting.

Applications

Developed under license from Schneider Electric, the PTQ-104 Client Communication Module incorporates proprietary backplane technology that enables powerful data access to the Quantum processor and can even be used in Quantum Unity Hot-Standby applications such as:

  • Power and distribution applications
  • Petrochemical
  • Water and Gas Applications
  • Oil and Gas production
  • SCADA and DCS applications

Especificaciones

  •  Single Slot - Quantum backplane compatible
  •  The module is recognized as an Options module and has access to PLC memory for data transfer
  •  Local rack - The module must be placed in the same rack as processor
  •  Compatible with all common Quantum programming packages, including Concept (version 2.6 or higher), Unity Pro (version 2.2 or higher), ProWORX (version 2.20 or later), and ModSoft.
  •  Compatible with Quantum Unity Hot-Standby systems.
  •  High speed data transfer across backplane provides quick data update times.
  •  Quantum data types supported: 0x, 1x, 3x, 4x
  •  High speed data transfer across backplane provides quick data update times.
  •  SPersonality Module - a non-volatile industrial-grade Compact Flash (CF) card used to store network and module configuration for easy disaster recovery, allowing quick in-the-field product replacement by transferring the CF card.

Hardware

 Specification

 Value

 Backplane Current Load

 1100 mA maximum @ 5 Vdc ± 5%

 Operating Temperature

 0°C to 60°C (32°F to 140°F)

 Storage Temperature

-40°C to 85°C (-40°F to 185°F)

 Relative Humidity

 5% to 95% (without condensation)

 Vibration

 Sine vibration 4 to 100 Hz in each of the 3 orthogonal axes

 Shock

 30 g, 11 ms in each of the 3 orthogonal axes

Dimensions (HxWxD), Approx.

250 x 40.34 x 103.85 mm
9.84 x 1.59 x 4.09 in

 LED Indicators

Active Status
Ethernet port Status
Battery Status
Debug/Config Port Activity
Module Status

 CFG Port (DEBUG)

 DB-9M PC Compatible
RS-232 only
No hardware handshaking

 Application Ethernet Ports

RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 sec, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

  

Certificaciones

Ex Certificate (ATEX Directive) 106,86 kB Última Modificación 11.11.2013
CE Mark 92,67 kB Última Modificación 10.09.2014
UL/cUL; Class 1, Div 2 1,18 MB Última Modificación 10.09.2014