Printer friendly version of this page. Find a Distributor near you.
SlotServer

LonWorks Communication Interface Module for ControlLogix by FieldServer Technologies

PS56-LON-001

Disponibilidad Limitada: Producto en stock limitado. More Info

The SlotServer LonWorks Open Interface allows an Allen Bradley ControlLogix platform to pass data between a ControlLogix CPU and a standard LonWorks communications network. The SlotServer Module provides a standard generic profile in LonWorks that allows most of the more common Standard Network Variable Types (SNVT’s) to be bound to the SlotServer for data transfer.

Physically configured to plug into a standard ControlLogix rack, the SlotServer Module is configured using standard RSLogix message block reads to allow for efficient transfer of large blocks of data.

SlotServer provides serial and Ethernet ports to enable ControlLogix interface to any of the many protocols available in the FieldServer driver library including BACnet, JCI Metasys, and a wide range of proprietary and legacy protocols used in the building automation, fire alarm panels and process control industries.

Comes with the standard two-year FieldServer warranty.

Características y Beneficios

Inherent to the design of LonWorks is the intention that all nodes residing on a LonWorks possess a profile which accurately describes the network variables (tags) available to the LonWorks network. This profile is declared to the LonWorks network by means of an External Interface File (XIF). This XIF remains unchanged for any particular profile. In other words, a change in the XIF is by definition a new profile.The PS56-LON-000 Open Interface profile for SlotServer provides a generic list of SNVT’s that can be used to bind the most common LonWorks data types to the SlotServer for data transfer. This document describes the fixed Open Interface profile for the SlotServer. The PS56-LON-001 is a LonMark compatible product, enabling the SlotServer platform to support other profiles. For further information, please contact ProSoft Technology and enquire about available Specific Profiles and other SlotServer Profiling Services. Input Tags from LonWorks to CPU (Data Table Read):

Tag Name

Tag Qty

LonWorks SNVT Type

SNVT Qty

amp_in

60

SNVT_amp

60

chiller_sts_in

45

SNVT_chlr_status

15

count_in

60

SNVT_count_f

60

count_inc_in

60

SNVT_count_inc_f

60

flow_in

30

SNVT_flow_f

30

freq_in

30

SNVT_freq_hz

30

hvac_mode_in

30

SNVT_hvac_mode

30

hvac_sts_in

105

SNVT_hvac_status

15

lev_disc_in

30

SNVT_lev_disc

30

obj_sts_in

60

SNVT_obj_status

30

occupancy_in

60

SNVT_occupancy

60

percent_in

180

SNVT_lev_percent

180

ppm_in

30

SNVT_ppm

30

press_in

60

SNVT_press

60

setpoint_in

180

SNVT_setpoint

30

state_in

90

SNVT_state

90

switch_in

360

SNVT_switch

180

temp_in

180

SNVT_temp_p

180

tod_event_in

45

SNVT_tod_event

15

volt_ac_in

60

SNVT_volt_ac

60

volt_in

60

SNVT_volt

60

Output Tags from CPU to LonWorks (Data Table Write):

Tag Name

Tag Qty

LonWorks SNVT Type

SNVT Qty

amp_out

60

SNVT_amp

60

chiller_sts_out

45

SNVT_chlr_sts

15

count_out

60

SNVT_count_f

60

count_outc_out

60

SNVT_count_inc_f

60

flow_out

30

SNVT_flow_f

30

freq_out

30

SNVT_freq_hz

30

hvac_mode_out

30

SNVT_hvac_mode

30

hvac_sts_out

105

SNVT_hvac_status

15

lev_disc_out

30

SNVT_lev_disc

30

obj_sts_out

60

SNVT_obj_status

30

occupancy_out

60

SNVT_occupancy

60

percent_out

180

SNVT_lev_percent

180

ppm_out

30

SNVT_ppm

30

press_out

60

SNVT_press

60

setpoint_out

180

SNVT_setpoint

30

state_out

90

SNVT_state

90

switch_out

360

SNVT_switch

180

temp_out

180

SNVT_temp_p

180

tod_event_out

45

SNVT_tod_event

15

volt_ac_out

60

SNVT_volt_ac

60

volt_out

60

SNVT_volt

60

Especificaciones

  •  Single Slot - 1756 backplane compatible
  •  The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  •  Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
  •  Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
  •  Local or remote rack

Hardware

Specification

Description

Slot width

Single

BackPlane Current Load

600 mA @ 5V

Operating Temperature

0o to 60 o C (32 o to 140o F)

Storage Temperature

-40o to 85o C (-40o to 185o F)

LED Indicators

Module Status

Backplane Transfer Status

Communications status

Configuration Error

System Error

Serial Activity

Ethernet Activity

10/100BaseT indicator

Connections

TP/FT-10 (LonWorks)

RS-485 (2-wire)

Ethernet (10/100BaseT)

Dimensions

Length: 5.11” (130 mm)

Depth: 2.27” (57,7 mm)

Height: 3.70” (94,0 mm)

Service Pin

For LonWorks commissioning

Mounting

Local or remote rack

Configuration

Configuration data is contained in

the configuration CSV file

downloaded to the module. Sample

configuration file is included.

Configuration file development

service available from FieldServer

Technologies or approved system integrators

Humidity

Up to 95% RH, with no condensation

Certificaciones

CE Mark 47,39 kB Última Modificación 06.05.2013
cUL/NRTL Certificate 127,38 kB Última Modificación 06.05.2013
Declaration of Conformity (RoHS/CE) 256,59 kB Última Modificación 06.07.2018