Simplify your operations - Booth #533 at Automation Fair® 2017 Find Out How
Printer friendly version of this page. Find a Distributor near you.
5201-DFNT-BACNET

EtherNet/IP to BACnet/IP Client Gateway

5201-DFNT-BACNET

Disponibilidad Limitada: Producto en stock limitado. More Info

The ProLinx EtherNet/IP to BACnet/IP Client Gateway creates a powerful connection between devices on an EtherNet/IP network and BACNET devices. This stand-alone DIN-rail mounted protocol gateway provides a single Ethernet port. The Ethernet/IP protocol driver supports the Explicit Messaging implementation of the protocol. User-configurable as both a Client and a Server, the EtherNet/IP port is a very powerful data transfer tool.

Características y Beneficios

Applications

The DFNT-BACNET modules are the ideal solution for the many applications where EtherNet/IP connectivity can be used to integrate with Ethernet-enabled BACnet devices. The BACnet/IP Edition 2 driver supports a single UDP client to interface with one or more devices that contain a BACnet server. The EtherNet/IP gateway is a powerful module designed with both Client and Server support, enabling easy connection to Rockwell Automation PLCs (CLX, SLC, PLC, CPLX, and similar devices). In combination with the BACnet device support, the module provides a very powerful interface to the many BACnet devices which are in use in the building automation and control marketplace today. EtherNet/IP (Explicit Messaging) Compatible Devices Rockwell Automation equipment that supports EPIC:

  •  PLC5/E rev C/N, D/E, E/D
  •  SLC5/05 series A, OS503 frn4
  •  1785-ENET Series A, rev D
  •  Interchange V6.2
  •  MicroLogix 1100/1400/ANY via 1761-NET-ENI
  •  CompactLogix 1768-L43/L45 via 1768-ENBT
  •  CompactLogix 1769-L32E/L35E/ANY
  •  CompactLogix L23E
  •  RSLinx Gateway V1.7+
  •  ControlLogix 1756-ENET/ENBT/EN2T/EN2TR

Aplicaciones

The DFNT-BACNET modules are the ideal solution for the many applications where EtherNet/IP connectivity can be used to integrate with Ethernet-enabled BACnet devices. The BACnet driver supports a single UDP client to interface with one or more devices that contain a BACnet server. The EtherNet/IP gateway is a powerful module designed with both Client and Server support, enabling easy connection to Rockwell Automation PLCs (CLX, SLC, PLC, CPLX, and similar devices). In combination with the BACNET device support, the module provides a very powerful interface to the many BACNET devices which are in use in the building automation and control marketplace today.

Especificaciones

The ProLinx Communication Modules provide connectivity for two or more dissimilar network types. The modules, encased in sturdy extruded aluminum, are stand-alone DIN-rail mounted protocol gateways, providing communication between many of the most widely used protocols in industrial automation today.

Hardware

Specification

Description

Power Supply

24 VDC nominal
18 to 32 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade

Current Load

500 mA max @ 32 VDC max

Operating Temperature

-4° F to 122° F (-20° C to 50° C)

Storage Temperature

-40° F to 185° F (-40° C to 85° C)

Relative Humidity

5% to 95% (with no condensation )

Dimensions

Standard:
 5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Extended:
 5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)

LED Indicators

Power and Module Status
Application Status
Serial Port Activity
Serial Port Error Status

Configuration Serial Port

DB-9M RS-232 only
No hardware handshaking

Ethernet Port (Ethernet modules only)

10Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Application Ports

Modbus Plus Connector
Two DB9 Female Standard Modbus Plus connectors

Serial Port Isolation

2500 V RMS port signal isolation per UL 1577
3000 VDC min. port to ground and port to logic power isolation

Shipped with Each Unit

Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)

Protocolos

DFNT Protocol Specification


The EtherNet/IP protocol driver supports the Explicit Messaging implementation of the protocol. User-configurable as both a Client and a Server, the EtherNet/IP port is a very powerful data transfer tool.


Protocol Specifications

The EtherNet/IP protocol is one of the primary connectivity tools to the different Rockwell Automation platforms. The Explicit Messaging aspect of the protocol (only) has been implemented in the ProLinx units to provide the data transfer link between the ProLinx units and the Rockwell Automation hardware.

General Protocol Information

Messaging

PCCC on CIP
Explicit Messaging supported

Miscellaneous

125 word read and write data lengths
Floating point data supported

EtherNet/IP Server Specifications

In Server mode, the module accepts commands from one or more clients to read/write data stored in the module's internal registers.

EtherNet/IP Server Specifications

Connections

Five independent TCP server sockets permit remote clients to interact with all data contained in the module.

Data File

Data Table File Start - Fixed at N10
Data Table File Size - 100 or 1000 words

CIP Services Supported

0x4C - CIP Data Table Read
0x4D - CIP Data Table Write

EtherNet/IP Client Specifications

In Client mode, the module controls the read/write data transfer between the gateway and other EtherNet/IP devices. Data transfer can be initiated and executed without any ladder programming being required in the Rockwell Automation hardware.

EtherNet/IP Client Specifications

General

One client

Command List

Support for 100 commands, each configurable for command, IP address, register to/from addressing and word/bit count.

Polling of command list

User configurable polling of commands, including disabled, continuous and on change of data (write only).

EtherNet/IP (Explicit Messaging) Compatible Devices

List of Rockwell Automation material that support EPIC:

  • PLC5/E rev C/N, D/E, E/D
  • SLC5/05 series A, OS503 frn4
  • 1785-ENET Series A, rev D
  • Interchange V6.2
  • MicroLogix 1100/1400/ANY via 1761-NET-ENI
  • CompactLogix 1768-L43/L45 via 1768-ENBT
  • CompactLogix 1769-L32E/L35E/ANY via 1761-NET-ENI
  • RSLinx Gateway V1.7+
  • ControlLogix 1756-ENET/ENBT/EN2T

BACNET Protocol Specification


Protocol Specifications

The BACnet/IP (Building Automation and Control networking) protocol is designed specifically to meet the communication needs of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems. The ProLinx BACNET driver implements a subset of the BACnet/IP protocol.

BACnet/IP Client Specifications

The module controls the read/write data transfer between the gateway and other BACnet/IP devices.

BACnet/IP Client Specifications

General

One client

Command List

Support for 100 commands, each configurable for command, IP address, register to/from addressing and word/bit count.

Service Port

1 to 65535

Function Code

12, 14, 15 and 16 (Read/Write Single & Multiple)

Data Type

0, 1, 3 and 4 (BO, BI, AO & AI)

Point Count

1 to 25


Certificaciones

Ex Certificate (ATEX Directive) 114,27 kB Última Modificación 11.11.2013
CB Safety 35,78 kB Última Modificación 27.08.2012
CE Mark 92,31 kB Última Modificación 22.02.2013
Russian GOST-R 7,07 MB Última Modificación 22.02.2013
GOST-R Declaration of Conformity 6,68 MB Última Modificación 22.02.2013
Korean KC Registration 807,00 kB Última Modificación 22.02.2013
UL/cUL; Class 1, Div 2 1,08 MB Última Modificación 02.07.2013